How Gearome checks a server rack

Gearome checks three things before you buy a rack, whether it will hold a closet’s network equipment, a NAS or a server. Your equipment has to fit in it. The rack and its shelves have to carry the weight. The power in the rack has to be enough for the equipment. When a check fails, the Gearome planner shows the two figures that decided it.

Catalog as of 281 products

Three verdicts, on the makers’ own figures

In the planner, a plan is the rack and the equipment you put in it, and each check on it ends in one of three verdicts. A Conflict means the figures prove the check fails. Unconfirmed means the figures cannot settle it: a figure is missing, or the answer turns on something the plan does not say yet. Otherwise the check passes.

The product pages for the catalog’s 281 products link 563 manufacturer documents, the ones their figures were read from.

One verdict, taken apart

A verdict names the rule it applied and the figures it compared, so you can check it against the documents yourself. A U decides how much equipment fits in a rack’s height. It is one unit of rack height, 1.75 inches.

Put a Synology RS422+, a NAS, in the StarTech RK12WALLO, a 12U open wall rack. The Gearome planner says this:

Too deep for the open wall rack

The NAS needs 12.9 inches of depth. The open wall rack’s mountable depth is only 11.9 inches, 1.0 inches less. Choose a rack with a mountable depth of at least 12.9 inches, or an open frame with nothing behind its rear rails.

The rule
Too deep for the open wall rack. Equipment deeper than the rack’s mountable depth does not fit. The mountable depth is the room from the front rail back to whatever stops the equipment: a back panel, a rear door or the wall.
The equipment
12.9 inches (327.5 mm), the depth of the Synology RS422+. Read from the Synology manual (PDF) (opens in a new tab), captured .
The rack
11.9 inches (303 mm), its mountable depth. Read from the StarTech datasheet (PDF) (opens in a new tab), captured . The rack itself is 12.0 inches (305 mm) deep, but that is not the figure the fit depends on.
The verdict
The Synology RS422+ is 1.0 inches deeper than the room the rack has. The figures prove it does not fit, so this is a Conflict.
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
The Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack, seen from the side The StarTech RK12WALLO, a 12U open wall rack on its wall, seen from the side, to scale, with U03 to U11 cut away. Its mountable depth, 11.9 inches (303 mm), runs from the front rail to the rear panel against the wall. The Synology RS422+, 12.9 inches (327.5 mm) deep, is drawn mounted at the front rail at U01, its body stopped by the rear panel. The part of it that does not fit, past the rear panel, is outlined in red. U03 to U11 not drawn NAS wall Mountable depth11.9 in (303 mm)Synology RS422+12.9 in (327.5 mm)
Side view of the StarTech RK12WALLO, a 12U open wall rack on its wall, cut between U02 and U12, with the Synology RS422+ at U01 and the part that does not fit outlined in red. The two depths and the U are measured and drawn to scale; the frame, the rail’s flange and the wall are sketched.

Both figures are in the manufacturers’ own documents, linked in the panel’s rows. The checks cover the rack and the equipment in it, not the room or closet the rack stands in, so whether a closet’s door shuts is yours to measure.

What each check compares

Each check compares a figure for the equipment with a figure for what holds or powers it: the rack, a shelf, or the power in the rack. The main ways a check can fail have names, set in bold below, and the planner prints each with the figures that decided it.

Fit: does it go in?

Fit has three parts: rack units, depth and mounting. A rack counts its U from the bottom, or out from the wall on a rack that holds equipment vertically, and each item on the rails takes a run of whole U. For equipment from the catalog, the depth check uses the depth the manufacturer publishes.

A rack’s rail span decides whether a rail kit fits the rack. It is the distance from the front rail to the rear rail. A rail kit is the pair of rails deep equipment slides in on, and it fits a range of rail spans. Where a rack’s rails adjust, they are set once for everything on them, and each item is checked at the setting they all can share.

FitThe Synology RS422+ in the StarTech RK12WALLO, a 12U open wall rack

12.9 in NAS the open wall rack takes 11.9 in

  • Rack units
    • Overlaps another item. Two items claim the same U.
    • No room left. An item runs past the rack’s top U.
    • Needs a taller rack. The equipment says it needs a rack of at least so many U, and the rack is shorter.
  • Depth
    • Too deep for this rack. The equipment is deeper than the rack’s mountable depth, as the Synology RS422+ is in the RK12WALLO, or its rail kit needs the rails further apart than the rack’s can go.
    • Rear rail can’t reach this equipment. Its rail kit needs the rails closer together than the rack’s can go.
    • No one rail span fits all of this. The items on the rails need rail spans that no one setting gives.
  • Mounting
    • Needs rear support this rack can’t provide. The equipment mounts on front and rear rails only, and the rack has no rear rail.
    • Not made to be rack-mounted. The equipment is on the rails, but it has no rack ears or rail kit.

Fit on a shelf

Equipment on a shelf is checked against the shelf. It stands on the shelf’s deck, the plate the equipment rests on, and takes U from the deck up, its height rounded up to whole U.

  • Too deep for what it rests on. The item is deeper than the shelf’s usable depth, the clear area it can stand on. Where we don’t have a shelf’s usable depth, we check against the shelf’s own depth.
  • More side by side than it is wide. The items on a shelf are wider together than its usable width.
  • No room above the surface. What stands on the shelf reaches past the rack’s top U.

Where a shelf’s deck sits inside its own U, as a cantilever shelf’s does, we allow 0.1 inches (2 mm) for the deck plate. Where we don’t know where a shelf’s deck is, we treat it as at the top. Our guide to rack sizes shows where each kind of shelf puts its deck.

Weight: will it hold?

A weight capacity decides whether a rack or a shelf can carry what is in it. It is the weight its maker rates it to carry. We check against the weight capacity the manufacturer publishes, for the conditions they state.

WeightThe UniFi USW-24 and the StarTech 1315B8H-RACK-PDU, a 1U PDU in the StarTech RK9WALM, a 9U wall cabinet

9.9 lb in the cabinet the cabinet is rated for 198.4 lb

  • Too heavy for this rack. Everything the rack holds weighs more than its weight capacity.
  • Holding more than it is rated for. What rests on a shelf weighs more than the shelf’s weight capacity.

What a rack holds is what is on its rails, its frame, its shelves, its roof and its floor. Each shelf’s own weight counts too. Equipment standing beside the rack does not count, and nor does the rack’s own weight. On an open frame, what stands on the floor under it does not count either. Heavy equipment belongs on the rails, or on a shelf rated for it.

When we have the rack’s own weight, the plan also shows what the wall or the floor carries: the rack’s own weight plus everything in it. We don’t check that total against the wall or the floor.

Some makers set a rule for the wall. StarTech asks for a wall that holds at least four times the weight of the rack with everything in it. Where the rack’s maker gives a rule like this and the rack is on a wall, the plan shows what the rule asks the wall to hold. That figure is the maker’s rule. We don’t know your wall, so we don’t check it.

A weight capacity can depend on how the rack is used. These are its load conditions: on the floor or on a wall, and stationary or rolling on its casters. The StarTech RK1236BKF, a 12U cabinet, is rated for 1763.7 lb (800 kg) standing still, but only 330.7 lb (150 kg) when moved with equipment in it. Both figures are from the StarTech datasheet (PDF) (opens in a new tab), captured .

Until the plan says how the rack is used, every weight capacity applies. At or under the lowest weight capacity, the check passes. Over the highest, it is a Conflict. Between them, it is Unconfirmed until the plan says whether the rack stands on the floor or a wall, and whether it will roll.

We have a weight capacity for every one of the 157 racks. 21 of them have a separate one for rolling.

Power: is there enough power?

A PDU puts outlets in the rack. It is a power strip for the equipment in a rack. A UPS keeps the equipment running when the power goes out. It is a battery between the wall outlet and the equipment. An item’s peak draw is the most power its manufacturer says it uses, and the plan’s power budget is what its PDUs and UPSs can supply between them.

PowerThe UniFi USW-24 on the StarTech 1315B8H-RACK-PDU, a 1U PDU

25 W peak draw the PDU supplies 1440 W

  • Over the power budget. The plan’s total peak draw is more than its power budget.
  • Doesn’t plug into the source that feeds it. A PDU or UPS fed by another has no input that fits any of that source’s outlets.
  • Doesn’t take the source’s voltage. A PDU or UPS fed by another takes its power in a different voltage range from the one that source puts out: 100 to 127 volts is one range, 200 to 240 the other.

When a UPS feeds a PDU, the pair can supply the smaller of the UPS’s watts and the PDU’s output capacity. A UPS and a PDU that do not feed each other add up. We add no margin: a total exactly at the budget passes. A plan with no PDU or UPS has no budget, so its power is not checked. Idle draw is shown, but not checked.

What each verdict means

A verdict says what the figures prove, and a missing figure gets a verdict of its own, Unconfirmed.

Conflict

A Conflict means the figures prove the check fails, as the Synology RS422+'s depth does in the RK12WALLO.

Unconfirmed

Unconfirmed means the figures cannot settle the check. That happens for one of three reasons:

  • a figure the check needs is missing;
  • the figures give a range, and the limit falls inside it;
  • the answer turns on something the plan does not say, such as whether the rack will roll.

A cabinet can give its rail span and not the room behind its rear rail. Equipment deeper than the rail span is then Unconfirmed in it: it may fit, and the figures cannot say either way. An Unconfirmed is not a milder Conflict.

In the planner, the bar above the drawing holds the plan’s Fit, Weight and Power figures. Beside them is a button that opens the Checks panel. For the example below, the button shows a question mark and the number 1, because 1 item is unconfirmed , and the panel it opens names the missing figure’s owner first, as the cause, then the equipment it leaves unsettled:

Example: the Dell PowerEdge R240 in the StarTech RK1224WALHM, a 12U wall cabinetThe cabinet’s rails span up to 20.0 inches (508 mm) with the rear rail fully back, and we don’t have the room it leaves behind that rail. The server reaches 22.6 inches (573.596 mm) behind its front rail, 2.6 inches more than the rail span, so whether it fits is Unconfirmed. We don’t have the server’s rail span either.

Checks

What each check found, and why.

Nothing in the plan supplies power, so power is not checked.

  • Fit

    Unconfirmed for 1 item

    Rack units

    Passed

    Depth and rail span

    The rack

    • Depth not confirmed

      This cabinet’s rails span 20.0 inches with the rear rail fully back. 1 item is deeper than that, and whether it fits depends on how much room the rack has behind its rear rail, which we don’t know.

    U01 · Dell PowerEdge R240

    • Rail span not confirmed

      We don’t have this server’s rail span, so we couldn’t check this server against the cabinet’s 2.4–20.0 inches. A rail kit’s sheet can give the rail span. This server can also hang on its front ears, which needs no rail span.

    • Depth not confirmed

      This server reaches 22.6 inches behind its front rail, 2.6 inches deeper than the 20.0 inches the cabinet’s rails span with the rear rail fully back. Whether it fits depends on how much room the rack has behind its rear rail, which we don’t know.

    Mounting

    Passed
  • Weight

    Passed
  • Power

    Not checked

For 68 of our 157 racks we don’t have the mountable depth as one figure, only a bound or nothing, so equipment can read Unconfirmed for depth in them. The same happens when we don’t have an item’s own depth, rail span, weight or peak draw.

Passes

A check that passes puts nothing on the item itself: no tick and no green. The pass is stated once, for the whole plan, on the button above the drawing and in the Checks panel. When every check settles, the button shows a tick and the panel lists each check as Passed:

Example: the UniFi USW-24 and the StarTech 1315B8H-RACK-PDU, a 1U PDU in the StarTech RK9WALM, a 9U wall cabinetThe switch is 7.9 inches (200 mm) deep, against the cabinet’s mountable depth of up to 14.6 inches (370 mm), and the two take 2U of its 9U. They weigh 9.9 lb, against the cabinet’s 198.4 lb (90 kg) weight capacity. The switch’s peak draw is 25 W, against the PDU’s 1440 W output capacity.

Checks

What each check found, and why.

  • Fit

    Passed

    Rack units

    Passed

    Depth and rail span

    Passed

    Least room behind: up to 6.7 in, behind UniFi USW-24, to the back of the cabinet, depending on how deep the cabinet is set.

    Mounting

    Passed
  • Weight

    Passed
  • Power

    Passed

Where the figures come from

We have figures for 281 products, and every one was read from a document its manufacturer publishes. Between them, the product pages link 563 documents: 251 datasheets, 129 product pages, 127 manuals, 43 drawings, 11 images and 2 FAQs.

Each product page links the documents its figures were read from, with the day we captured each one. Where a product page lists more than one document, each one after the first names the figures it gave. A capture date says when we read the document. The manufacturer may have changed it since.

Where none of our documents states a figure, we leave it out. The product page shows no row for it, and for a power draw a dash where the watts would be. A check that needs it is Unconfirmed.

The catalog is as of , the newest day we read a document behind one of its figures. The oldest capture is from .

The catalog is small: 134 of its 281 products are StarTech.

Whose figures a check uses

The word beside an item in a plan, Catalog or Custom, says whose figures its checks used.

Catalog
Figures read from the manufacturer’s documents. They are the same for everyone, and the product page links the documents.
Custom
Figures entered by hand, by whoever built the plan. No document stands behind them, so nobody else can check them.

A custom item is equipment someone defined by hand, from its label, instead of choosing it from the catalog. Add one for equipment we don’t have figures for. It needs its height in U, and takes the figures its kind is checked on, such as its depth, weight and peak draw. A figure left empty makes a check that needs it Unconfirmed. A custom item is checked by the same rules, and a verdict on it is only as good as the figures entered.

What a saved plan’s link opens on

Saving a plan gives it a link. Anyone with the link can open the plan for 30 days after its last save.

On any browser but the one that saved it, the link opens on the plan’s summary, written for whoever didn’t build the plan. It says the plan in a sentence or two, draws its rack and gives the three checks’ figures, then each check under the verdict it reached. Each figure says whose its limit is. For the UniFi USW-24 and the 1315B8H-RACK-PDU in the RK9WALM, the summary reads:

A switch and a PDU go in the StarTech RK9WALM, a 9U wall cabinet. It fits, the cabinet can carry it and the PDU supplies enough power.

Fit: passed. 2 of 9U used.

9U is StarTech’s figure for the cabinet.

Weight: passed. 9.9 lb of a 198.4 lb weight capacity.

9.9 lb against StarTech’s weight capacity of 198.4 lb.

Power: passed. Peak draw 0.03 kW of a 1.44 kW power budget.

0.03 kW of the 1.44 kW StarTech’s PDU can supply.

Passed

Fit. Everything fits in the cabinet, depth included. The items take 2U of its 9U, so 7U are left. The least room behind an item is up to 6.7 inches, behind the switch, to the back of the cabinet, depending on how deep the cabinet is set.

Weight. The cabinet can carry what is in it. It is rated for 198.4 lb, and the equipment weighs 9.9 lb, so 188.5 lb is left.

Power. The PDU supplies enough power. It can supply 1.44 kW, and the peak draws come to 0.03 kW, so 1.41 kW is left.

Not checked

Heat. At peak draw, the equipment gives off about 25 W of heat, 85 BTU an hour.

Circuit. What the PDU plugs into. The plan’s peak is 0.2 A at 120 V, with every item at its peak draw.

Wall. What the cabinet hangs on, and what fixes it there.

Cable room. The room the power cords and cables need behind the equipment.

The summary’s Open the plan button leads to the planner and its Checks panel, where each Conflict and Unconfirmed has its figures. After the checks, the summary says which of each custom item’s figures were entered by hand and which are blank, so whoever opens it knows which ones nobody else can check. Whoever built the plan sees the same summary from the plan’s status menu.

Whoever opens the link can change what is on screen. Saving those changes gives them a link of their own, and the plan they were sent stays as it was. Only the browser that saved a plan can change it in place or delete it.

What Gearome does not check

Some questions that decide an order are outside the three checks. These stay yours to settle.

Fit: what the three parts do not cover

  • Room behind the equipment for plugs and cables, and any part the manufacturer’s depth figure leaves out, such as a front bezel or a second power supply. Our guide to server rack depth says how to allow for them.
  • Which holes a rack’s rails have, and the cage nuts or screws that fit them.
  • Where a frame-mounted item, such as a vertical PDU, fixes, and which rail holes it uses.
  • A shelf’s width, where we don’t have it or an item’s width. That item is left out of the width check, so the check can pass without it.
  • Items standing one behind another on a shelf. Each is checked against the shelf’s usable depth alone.

Weight: what the weight capacity does not cover

  • How the weight is spread in the rack, and whether it can tip.
  • Whether a wall, and the screws and anchors in it, can hold a wall-mounted rack. Where the rack’s maker sets a rule for the wall, the plan shows what it asks, as the maker’s rule.
  • Whether the floor can carry a loaded rack.
  • The weight each slide rail kit is rated for.
  • The weight of rail kits and mounting hardware. They are not items a plan can hold yet, so leave room for them under the weight capacity.

Power: what the budget does not cover

  • How many outlets there are, or whether equipment’s plugs fit a source’s outlets. Only a source fed by another source is checked for its plug.
  • How long a UPS can run, or its VA rating: the volt-amperes a UPS lists beside its watts. The watts decide what it can supply.
  • Whether the wall circuit can supply what the PDUs and UPSs draw.

Everything else

  • Airflow, heat and noise.
  • Cables, network ports and PoE, the power some network ports send to the device on the other end of the cable.
  • Whether the rack fits its room or closet, the swing of its door included.

Not covered at all: 10-inch racks, and network details such as IP addresses and VLANs. Those belong in a documentation tool once you own the equipment. Gearome shows no prices yet.

Before you order, check these yourself

  • Every custom item’s figures. We have only what was entered.
  • Every Unconfirmed item. A figure it needs is missing, or the plan has not said how the rack is used.
  • Everything under What Gearome does not check.

To run these checks on your own rack and equipment, start a plan. There is nothing to sign up for.