Server rack accessories: what do you need?

Your equipment decides which server rack accessories you need. Equipment made for a desk, such as an ISP’s modem in a closet, needs a shelf. A long item that has to be held at the front and the back needs a rail kit. Anything that plugs in needs outlets at the rack, from a PDU or from a power strip on a shelf.

Published Last updated

What do you need besides the rack?

The shelf, the rail kit and the rest are rack accessories. The table below gives the U each one takes, so add those U up before you choose the rack’s height. A U is one unit of rack height, 1.75 inches (44.45 mm). Each accessory adds weight too, and some draw power.

Rack ears decide whether an item needs a shelf. They are the brackets that screw an item to the front rails. A PDU puts outlets in the rack. It is a power strip for the equipment in a rack. A UPS keeps the equipment running when the power goes out. It is a battery between the wall outlet and the equipment.

Either the rack’s box or the equipment’s box can already hold some accessories, so read what is in each before you order.

What else an order may need

What decides whether you need each item, and how much of the rack it takes.

ItemYou need it whenTakes
ShelfAn item has no rack earsIts own U, and the U above when its deck is at the top of its U
Rail kitAn item has to be held at the front and the back, and came without a kitNo U of its own
Cage nuts and screwsThe rack came without enough: cage nuts for square holes, screws for any holesNo U
PDUAnything in the rack plugs inIts own U on the rails, no U on a post or side bar, or space on a shelf
UPS (battery backup)Equipment has to keep running through a power outageIts own U if it is rack-mount, or none for a tower beside the rack
Patch panelNetwork cables from other rooms end at the rackIts own U
Cable managerCables would otherwise hang across the equipmentIts own U on the rails, or no U on a post or side bar
Fan panelA cabinet needs help moving warm air outIts own U
Blanking panelWarm air could return to the front of a cabinet through empty UThe U it covers
A KVM console, a screen and keyboard made for a rack, takes its own U as well.

Which shelf fits your server rack?

Your rack’s rails decide which shelf fits. A shelf holds equipment that has no rack ears, such as a desktop NAS, a mini PC or a modem. Our page for each rack lists its Posts, the upright bars that carry the rails. A 2-post rack has front rails only, and a 4-post rack has front and rear rails. Some racks also have side bars that run between the posts, along the rack’s sides. On a wall cabinet’s listing, look for rails at the back as well as the front. Our rack catalog filters by Posts, and our rack shelf catalog lists the shelves we have figures for.

A cantilever shelf bolts to the front rails only and reaches back into the rack from them. Any rack with front rails can take a cantilever shelf no deeper than the rack’s mountable depth. A center-mount shelf bolts to the front rails at its middle and reaches toward the front and the back of the rack. In a cabinet, the part in front of the rails has to fit the cabinet’s front clearance. That is the room between the door and the front rails. A 4-post shelf bolts to the front rails and the rear rails. A sliding shelf pulls out of the rack like a drawer, and its spec sheet says which rails it bolts to.

A rack’s rail span is the distance from its front rail to its rear rail. The rack’s outside depth is more than its rail span, as our guide to server rack depth explains. A 4-post shelf’s spec sheet can give the rail span range it fits. The range has to include a distance the rack’s rails can be set to.

A shelf of any of these kinds can be vented, so air passes through it.

Example StarTech ADJSHELF, a vented 4-post shelf
Bolts to
front and rear rails
Rail span
19.5 to 38.3 in (495 to 974 mm) As StarTech’s datasheet calls it: “Adjustable Mounting Depth”
Deck
the plate the item stands on, at the top of its U, so the item starts in the U above
The ADJSHELF fits a rack whose rails can be set to a distance within 19.5 to 38.3 inches (495 to 974 mm). A rack with front rails only gives it nothing to bolt to at the back, so that rack takes a cantilever shelf.

Then check the shelf against the item that will stand on it. The shelf’s deck is the plate the item stands on, and the item takes U from the deck up. A cantilever shelf’s deck is at the bottom of its U, so the item starts in the shelf’s own U. A 4-post shelf’s deck can be at the top of its U, so the item starts in the U above it. How many U the item takes is in our guide to what size rack you need.

The shelf’s usable depth and usable width are the length and width of the clear part of the deck. The mounting flanges, the edges that bolt to the rails, take some of the shelf’s size, so these are smaller than the shelf itself. The item has to be no deeper than the shelf’s usable depth, with room behind it for its plugs and cables. Items side by side have to fit its usable width together. Items that stand one behind another add up. Their depths, and the room behind each for its plugs and cables, together have to fit the shelf’s usable depth. The Gearome planner adds up the widths of the items on a shelf. It checks each item’s depth on its own, so add up the items that stand one behind another yourself. Where we don’t have a shelf’s usable depth, it checks against the shelf’s own depth, as How it works explains. Together, the items’ weights have to be within the shelf’s weight capacity.

Does your equipment need a rail kit?

You need to buy a rail kit when your equipment has to be held at the front and the back and didn’t come with one. The equipment’s spec sheet can say so, as the example below does. A rail kit holds a long item, such as a server, at the front rail and the rear rail. Some rack-mount equipment mounts on its rack ears alone and needs no kit.

A kit made for a 4-post rack needs rear rails, so it can’t go in a 2-post rack. Some kits fit a 2-post rack too, and the kit’s spec sheet can say which racks it fits. The kit’s spec sheet can also give its rail span range, which has to include a distance the rack’s rails can be set to. Our guide to server rack depth explains which figure is a rack’s rail span.

A sliding kit lets the item pull out like a drawer, and a fixed kit holds it in place.

Example Synology RS822+, a rack-mount NAS
Rack
“4-post 19" rack” As Synology’s spec sheet prints it
Rail kit
“sold separately” The RKS-02 “Sliding” kit, or the RKM114 “Mounted” kit, a fixed one
Synology’s spec sheet says the RS822+ goes in a 4-post rack on the RKS-02 or the RKM114 rail kit. Synology sells both kits separately. So for this NAS, you buy one of the kits, and choose a rack with rear rails.

Cage nuts or threaded holes?

Your rack’s rail holes decide whether you need cage nuts. Rails with square holes take cage nuts, also sold as captive nuts: one clips into each hole, and the screw goes into the nut. Rails with threaded holes take the screw directly.

A rack’s spec sheet or the manufacturer’s page can name its holes, as the example below does. The spec sheet or the page can also list the cage nuts and screws in the box. Read that list before you order more cage nuts or screws. Some rack-mount equipment comes with its own screws and cage nuts too. The equipment’s manual can say how many screws each item uses.

Example NavePoint 00405918, a swing-gate wall rack
Rail holes
“Cage Nuts and 12-24 Threaded” As NavePoint’s product page prints it
In the box
“10 x M6 Cage Nuts, 10 x M6 Screws, 10 x 12-24 Screws”
NavePoint’s manual says this rack’s rails can be fitted facing forward with their square holes or with their threaded holes. M6 and 12-24 are two screw sizes. The M6 screws go into the cage nuts, and the 12-24 screws go straight into the threaded holes. With the threaded holes forward, you need 12-24 screws only. With the square holes forward, you need a cage nut for every screw. Decide which side faces forward before you order. Then count what your equipment uses against what is in the box.

Which PDU and UPS does a server rack need?

Everything in the rack that plugs in needs an outlet, and a PDU (power distribution unit) is one way to put them there. Each item’s peak draw is the most power it draws. Add up the peak draw of everything plugged into the PDU. The sum is the total peak draw, and it has to be within the PDU’s output capacity, the most power the PDU can supply.

Check the plug on each item’s power cord against the PDU’s outlet type. A NEMA 5-15R outlet takes the everyday North American three-prong plug. An IEC C13 outlet takes the C14 plug of a jumper cord, a short cord that runs from the PDU to the item. Check the PDU’s own input plug against the wall socket or the UPS it plugs into, and check that the PDU’s power cord reaches it. The Gearome planner doesn’t check cord lengths.

A horizontal PDU bolts to the rails and takes U. A vertical PDU fixes to the rack’s posts or side bars and takes none. A vertical PDU’s spec sheet can give the rack height it needs, so check it against your rack’s height in U. A power strip that isn’t made for a rack can lie on a shelf, like other equipment without rack ears. Our rack PDU catalog lists the PDUs we have figures for.

A UPS can sit between the wall and the PDU. A rack-mount UPS takes U and adds weight like any other equipment. When a UPS feeds the PDU, the PDU can supply no more than the UPS supplies. A UPS gives two ratings: watts, and VA (volt-amperes), the larger figure. Compare the UPS’s watts with the total peak draw, not its VA. The Gearome planner checks the total peak draw against what the PDU and the UPS can supply, as the page How it works explains. It doesn’t check how long a UPS can run.

Do you need a rack cable manager or a patch panel?

A cable manager holds your cables in order, so they don’t hang across the equipment. A horizontal cable manager bolts to the rails and takes U. A vertical one can fix to the rack’s side bars and take no U, or bolt to the rails and take U. A vertical cable manager on the side bars can need a tall rack, as a vertical PDU does.

Two StarTech vertical cable managers

Where each one fixes, and how much of the rack it takes.

Cable managerFixes toTakesRack height
StarTech CMVER20UFHoles built into the rack, or the rack’s side barsNo U20U or taller
StarTech CMHOOK1UThe rack’s rails1UAny height
StarTech’s datasheet says the CMVER20UF fixes to keyhole-shaped holes built into the rack, or to the “horizontal mounting rails” along the rack’s side. Those are the rack’s side bars. StarTech names the equipment rails as a fallback for a rack with neither, and doesn’t say how many U it then takes. Check which your rack offers. The CMHOOK1U bolts to the rails, and takes U like other equipment.

Some racks come with cable hooks, so read what is in the rack’s box before you buy a cable manager.

A patch panel is where the network cables from your walls end. If every cable starts and ends inside the rack, you don’t need one.

Does your cabinet need fan panels or blanking panels?

A cabinet is a rack with doors and side panels. It can need a fan panel when its doors and side panels are solid and it came without fans. Nearly all the power your equipment draws ends up as heat. Solid doors and side panels can hold that heat in, and perforated ones let air through. An open frame has no doors or sides to hold it.

The total peak draw you add up for the PDU is the heat a cabinet has to move. We don’t have a figure for how much heat a cabinet lets out, so this guide doesn’t size its fans. The Gearome planner doesn’t check the airflow in the cabinet or in the room around it. Some cabinets name their door in the product’s name on the listing. If the name doesn’t, or for the side panels, read the listing. Some cabinets come with fans, so read what is in the box.

Example Tecmojo 11110102, a 9U wall cabinet
Door
“Glass Door” On Tecmojo’s listing
Fans
“2 Cooling Fans”
Tecmojo’s listing says the cabinet has a glass door, which is solid, and 2 cooling fans. We don’t have how much air the fans move.

A fan panel moves air through a cabinet. An exhaust fan pushes warm air out, and an intake fan draws cooler air in.

Two AC Infinity fan panels

The exhaust version and the intake version of one design.

Fan panelMoves airAirflowTakesPeak draw
CloudPlate T7Out of the cabinet220 CFM2U10 W
CloudPlate T7-NInto the cabinet220 CFM2U10 W
Each ships with its own rack screws and cage nuts.

A blanking panel, also sold as a filler panel or a blanking plate, covers an empty U at the front of a cabinet. A solid one stops warm air from the back returning to the front through the gap. So the air the cabinet’s fans move goes through the equipment. A vented blanking panel covers the U but lets air pass through it. A solid or a vented one also gives the front a closed look.

How to work out what else to buy

Work out what else to buy in these steps.

Your space and your items

  1. Measure the space the rack or cabinet goes in, with any closet door shut.
  2. List each item you own, and how it mounts: rack ears, a rail kit, or neither.
  3. Add what the items need: any rail kit not in the box, a shelf for items without ears, and outlets for what plugs in.
  4. Add up the U, the weight and the peak draw, counting the accessories too.

Choosing the rack

  1. Choose a rack with the rails your items mount on, at least that many U, and a weight capacity above the total weight. On a wall, the wall and its screws and anchors carry the weight too, as our guide to server rack weight capacity explains. The Gearome planner doesn’t check them.
  2. Check the deepest item against the rack, and the rack’s outside size against your space, as our guide to server rack depth explains.
  3. Choose the kind of shelf the rack’s rails take.

Ordering and checking

  1. Read what comes in the rack’s box.
  2. Order the cage nuts, screws and cable management the box doesn’t hold.
  3. Check the total peak draw against the PDU’s output capacity, or the UPS’s when it is lower.

The example below works through three items.

Three items to put in a rack

What each item needs to go in, from its spec sheet.

ItemHow it mountsWhat it adds to the order
Synology RS822+ NASA rail kit, front and rearA rail kit, sold separately
UniFi USW-24 switchRack earsNothing
Home Assistant Green smart-home hubNo rack earsA shelf
All three items plug in, so the order needs three outlets. A power strip on the shelf beside the hub would give them. This example bolts a PDU to the rails instead, to show how a PDU’s output capacity is checked. The PDU takes 1U and gives 8 outlets. The NAS’s rail kits are made for a 4-post rack, so the rack needs rear rails. A 4-post rack can take a cantilever or a 4-post shelf. This example uses a cantilever one, since the hub is small and a cantilever shelf has no rail span to match.
Example StarTech 4POSTRACK8U, a 4-post open frame rack
Rails
front and rear, 22.0 to 40.0 in (560 to 1017 mm) apart
Rail holes
“Square (For Cage Nut)” As StarTech’s datasheet prints it
In the box
“24 - M6 Cage Nut”, “24 - M6 Screw” and “4 - Cable Management Hook”
This rack has rear rails, so the NAS’s rail kit has something to bolt to. We don’t have the rail span of Synology’s rail kits, so check the kit’s spec sheet before you order. Its rail span range has to include a distance within this rack’s 22.0 to 40.0 inches (560 to 1017 mm). The rack’s box holds 24 cage nuts, 24 screws and cable hooks, so the order needs no cable manager. Count the screws each item and the rail kit use, from their manuals, against those 24 before you order more.
The order in a StarTech 4POSTRACK8U

Each item from the bottom of the rack up, with what it takes, weighs and draws.

ItemUWeightPeak draw
APC AP7800B PDU Bought for the three plugs. It supplies the power1U3.8 lb (1.73 kg)Not added
Synology RS822+ NAS On its rail kit. Synology’s “Access” draw, not its peak1U14.1 lb (6.4 kg)≥47.69 W
UniFi USW-24 switch1U6.2 lb (2.79 kg)25 W
StarTech CABSHELF1U shelf Bought for the hub1U2.7 lb (1.225 kg)0 W
Home Assistant Green hub Stands within the shelf’s 1U. Home Assistant’s “Load” draw, not its peak0U0.7 lb (0.34 kg)≥3 W
Total4U≥27.5 lb (12.49 kg)≥75.69 W

The order takes 4U of the rack’s 8U, which leaves 4U free.

It weighs at least 27.5 lb (12.49 kg), since we don’t have the rail kit’s weight. That is up to 633.9 lb (287.51 kg) under the rack’s rolling weight capacity of 661.4 lb (300 kg).

The hub’s 0.7 lb (0.34 kg) is 32.3 lb (14.66 kg) under the shelf’s weight capacity of 33.1 lb (15 kg). The hub is 4.4 inches (112 mm) deep, 2.6 inches (66 mm) less than the shelf’s own depth of 7.0 inches (178 mm). The hub’s depth doesn’t count its plugs and cables, and they need room behind it in that 2.6 inches (66 mm). We don’t have the shelf’s usable depth, which is smaller, so check the hub against it on the shelf’s spec sheet.

The NAS is 19.4 inches (492.6 mm) deep, 2.7 inches (67.4 mm) less than the 22.0 inches (560 mm) this rack’s rails are apart at their closest. So it fits between them at any setting. Its depth doesn’t count the plugs and cables at its back, and the open frame leaves them room behind the rear rails.

Synology gives the NAS’s draw in use, its “Access” figure, and no peak draw. Home Assistant does the same for the hub, with its “Load” figure. So the order’s total peak draw is at least 75.69 W. The PDU’s output capacity of 1440 W is at most 1364.31 W more than that draw. APC’s datasheet gives the PDU “8 NEMA 5-15R” outlets and a “NEMA 5-15P” plug, for an everyday North American wall socket. The three plugs take 3 of its 8 outlets. The Gearome planner doesn’t count outlets, so count them for your own equipment.

The Gearome planner runs the fit, weight and power checks on your own rack and equipment. It checks whether the rack has the rails each item mounts on, and whether a shelf is deep enough. It checks the weight against the rack’s and each shelf’s weight capacity, and the total peak draw against the PDU and the UPS. The page How it works lists each check, with what it leaves to you. For equipment we don’t have figures for, add a custom item with your own measurements.